During the final construction phases of a new pre-clinical research facility, dense structural building materials blocked critical emergency radio signals. This wireless coverage gap dropped signal strength below mandatory regulatory baselines, creating a severe life safety risk and stalling the building’s final occupancy permit. Midwest Alarm Services engineered and deployed a code-compliant Emergency Responder Communication Enhancement System (ERCES) utilizing a custom distributed antenna layout. This targeted low-voltage communication intervention eliminated the signal dead zones, satisfied all local fire code requirements, and successfully cleared the facility for its scheduled opening.

During the final stages of the construction for a state-of-the-art research facility in the Midwest region, a critical safety gap emerged. The building’s modern construction materials, including masonry walls, specialized refrigeration units, and extensive metal ductwork, significantly blocked essential over-the-air (OTA) wireless communications.

An ERCES (in-building radio amplification system) is required because many buildings with concrete, steel, low-E glass, or underground areas can block or weaken public safety radio signals. Under the 2015 International Fire Code (IFC) Section 510, buildings must provide approved emergency responder radio coverage. This is enforced because consistent radio communication is critical for incident command, firefighter safety, and timely rescue operations.

First responder public safety radio signals were not penetrating the building’s interior. An initial engineering survey confirmed widespread communication failures, with signal strength falling significantly below the mandatory -95 dBm threshold. This severe lack of reliable, two-way communication created a critical life safety and compliance issue, impacting the ability of emergency personnel to communicate during a crisis.

At the direction of The Construction Manager and in collaboration with The Electrical Contractor, Midwest Alarm Services (MWAS) was contracted to immediately resolve this compliance and safety issue.

MWAS designed and implemented an Emergency Responder Communication Enhancement System (ERCES), also known as a Bi-Directional Amplifier (BDA). This indispensable solution is specifically designed to eliminate communication dead spots caused by modern building materials.

  • Initial Survey: MWAS utilized industry-recognized equipment (such as PCTEL’s SeeHawk “Public Safety Network Testing Solution”) to complete an engineering survey, measuring RSSI (Received Signal Strength Indicator) and SINR (Signal to Noise Ratio) to precisely map all dead zones in the facility.
  • System Design: The ERCES was engineered to capture the weak public safety signal using an external antenna and route it to a powerful booster unit.
  • The DAS Network: The amplified, enhanced signal was distributed throughout the facility via a Distributed Antenna System (DAS) strategically installed to eliminate all signal attenuation.

A Distributed Antenna System (DAS)

The implementation of the MWAS ERCES solution delivered immediate and verifiable success, assuring the facility owners and local authorities that critical emergency communications were secured.

MetricPre-Enhancement (Failure)Post-Enhancement (Pass)Improvement
Required Signal ThresholdWeaker than -95 dBmStronger than -95 dBmCompliance Achieved
Worst Measured Signal-119 dBm-53 dBmMajor Signal Boost
Average Signal ReadingIn the -100 to -115 dBm rangeIn the -70 to -85 dBm rangeClear Communication

Pre-Enhancement Test “FAILED”

Chart showing widespread signal failures.

Widespread signal failures, with many areas deep in the red zone.

Pre-Enhancement Test “PASSED”

Chart showing excellent signal strength.

100% green coverage, confirming excellent signal strength.

After all areas of the facility were confirmed as adequate by the MWAS test equipment, local Fire Department and Building Department officials met for a final radio test. Two-way radio transmissions were confirmed as excellent throughout the facility.

“Two-way radio transmissions were confirmed as excellent throughout the facility, assuring timely emergency responder communications.”

By quickly delivering a certified ERCES solution, Midwest Alarm Services ensured the client’s compliance with critical life safety regulations, providing the necessary infrastructure to maximize first responder effectiveness during any potential emergency.